Last week’s Microsoft 365 outage started on a path built to keep services running. A routine Teams failover landed on a gateway already short of capacity, and the partitions meant to contain the damage did not hold. AWS lost IAM Identity Center sign-in in us-east-1, and the FAA’s initial investigation points to traffic from two sites, one where a new router was being deployed, for the flood that grounded US flights. Lithuanian Customs took its sign-in portal offline to contain an attack, and several of the week’s breaches hit suppliers, acquired systems or subsidiaries.
Microsoft 365: failover onto a gateway already short of capacity
Microsoft’s preliminary post-incident report for EX1550543 and MO1550821 is dated November 15. Microsoft issues these reports to tenants in the Microsoft 365 admin center, and the copy cited here was published by Next.ink. It puts the incident at 4:20 p.m. UTC on November 12 to 4:10 p.m. UTC on November 13. Most users could not reach their Exchange Online mailboxes through Outlook or other mail clients, mail delivery was delayed for many users, and Exchange-dependent features of Teams, Copilot and other services were affected1. Microsoft had not published a final report when this issue went out, so this section rests on the preliminary one.
Microsoft names three factors. The first is a latent defect in a fix prepared in July specifically for the Microsoft 365 networking gateway servers: under certain load, lock contention inside an internal Windows process exhausted CPU and memory. Microsoft says neither the defect nor the fix applies to broader Windows deployments. Load tests missed it because they used weaker hardware with fewer cores, and the contention is worse on newer machines with more cores. The second factor is load. At 1:07 a.m. UTC on November 12 an automated failover moved Teams from the alternative gateway onto the primary gateway that also serves Exchange Online, a type of failover Microsoft calls part of normal operations. The third is capacity: nearly 14% of the gateway’s servers were out of service because of an unrelated issue from the previous day. Microsoft says that loss had no impact on its own1.
Correction, November 23, 2026: Microsoft’s final post-incident report says this capacity was out of service as part of routine operations while the latest version of the service was being deployed, not because of an unrelated issue. The incident report for November 16 to 22 covers the final report.
Together they triggered the defect during the peak window of US traffic. Traffic management moved users from failing servers to healthy ones, which spread the same load over fewer servers and pushed them into the same failure. In less than two hours the defect had been hit across the fleet, and at the lowest point more than 80% of the gateway servers were unresponsive. The gateway is built from thousands of capacity units grouped into regions, and the bulkheads between those partitions should have stopped a cascade. Because of a separate issue, they did not, and the impact spread across the gateway worldwide. Teams, OneDrive, SharePoint and the Office apps moved off the faulty gateway and were partly restored earlier, while Exchange Online cannot fail out of it for scale reasons1.
Servers returned to service were overwhelmed by the waiting traffic and went down again, and a defect months old could not be reverted quickly with the usual rollback, flighting or feature flags. From 7:20 a.m. UTC on November 13 Microsoft rolled out an update restoring the earlier code path, group by group, extended the mail delivery window so delayed messages were not returned as undeliverable, and added capacity and guardrails on traffic distribution1.
Status: confirmed by the vendor, cause preliminary. Our recommendation is to size a failover target for the failover load plus whatever is already out for maintenance or failure, counting CPU, memory, network and placement rules, not only hosts. Test labs need the core counts and hardware generations of production. A containment boundary, whether clusters, edge clusters or availability zones, counts only if it has been tested with the failure it is meant to stop. Plan the restart too: bring capacity back behind rate limits, and keep incident communications off the mail system that is down.
AWS us-east-1: sign-in first, one zone last
On November 15, between 3:05 and 6:10 a.m. PST, AWS saw signup errors, authentication failures and connectivity issues in us-east-1. Sign-in through IAM Identity Center to the AWS Console and to services such as Amazon Connect failed. Authentication was fully mitigated at 5:20 a.m. PST. A subset of Network Load Balancers in a single cell of one Availability Zone, use1-az1, kept losing connectivity until 6:21 a.m. PST, and during the event AWS advised customers who needed immediate resolution to create a new load balancer with targets in multiple Availability Zones2.
Status: confirmed by the vendor. AWS has not disclosed a cause and has not published a post-event summary, so what follows is general advice, not a finding. Our recommendation is to keep break-glass access that depends neither on the external identity provider nor on the federation service in front of it, here IAM Identity Center. For vCenter, NSX, SDDC Manager and backup consoles that means local accounts or host-level access with protected credentials, MFA where the product supports it and an alert on every use, tested on a schedule. For load balancers, check which zones are enabled, the healthy target capacity in each zone and the cross-zone setting, and rehearse moving traffic out of one zone.
FAA: traffic from two suspected sites, a nationwide ground stop
At about 3:30 p.m. ET on November 13 the FAA issued a nationwide ground stop, and traffic resumed at 8:15 p.m. The FAA says its legacy equipment became unstable when data flooded the FAA Telecommunications Infrastructure network at 1,000 connection attempts every 4 to 5 seconds, creating instability in aircraft communications and radar feeds. Instability hit 17 of the 22 Air Route Traffic Control Centers, about 3,500 aircraft in the air landed safely, and operators canceled more than 12,000 flights on Friday, November 13, not all because of the ground stop3.
The initial investigation points to two potential sources, a radar site in Amarillo, Texas, and a radio communications site in El Dorado, Arkansas, where the network service provider L3Harris had been deploying a new router. When L3Harris blocked both sites, the network stabilized, and the broadcasting function was disabled on all the new routers as a precaution. The FAA will reevaluate when such routine work is scheduled. It found no indication of a cyberattack, and the FAA and L3Harris are still investigating the root cause3.
Status: confirmed by the government, root cause open. Our recommendation is to treat a provider’s field work at one site as a change to the whole network it joins. Rate limits suited to each protocol, storm control on the interfaces that support it and protection for the systems least able to absorb a flood limit how much one site can push into the core, provided they have been load-tested. Monitoring should show a flood within minutes, and isolating one site should be a rehearsed procedure: the FAA’s network stabilized once the two suspect sites were blocked.
Lithuanian Customs: a sign-in portal suspended to contain an attack
Lithuanian Customs detected a cyber incident on November 10 and suspended its Common User Management Portal (BAP), the sign-in service for Lithuanian and European Commission customs systems. By November 13 it had found that personal data of users who logged in on November 9 or 10 may have been affected and was contacting them directly. With BAP down, Commission systems such as POUS and ICS2 were unreachable for individuals and small businesses that authenticate through it. The authority isolated connections to the affected infrastructure, preserved data for the investigation and brought in external specialists4. On November 16 it reported that the investigation had confirmed unauthorized access to BAP and that access was restored through the Electronic Government Gateway, with certificate login not yet available and service addresses moved to a new domain5.
Status: confirmed by Lithuanian Customs, entry path not disclosed. The authority describes isolating connections and preserving evidence before a secure restoration. Our recommendation is to scope containment to the evidence: restrict the compromised component, review existing sessions, application credentials and other ways in, and preserve evidence before restoring. List what depends on your central identity service, from vCenter and NSX to backup and ticketing, decide which of those can run degraded with local accounts, and rehearse a staged restore in which some login methods come back late, as Lithuanian users saw.
Suppliers, acquisitions and subsidiaries
Maersk said on November 11 that it had found unauthorized access and data extraction from “one of our local legacy systems from a previous acquisition.” It says the incident is isolated, its findings so far suggest no sensitive data was disclosed, and it sees no impact on other systems or on customer integrations such as APIs and EDI6. The extortion group WhiteArmor claims to hold about 100 GB from the platform of the former LF Logistics and demands USD 5 million7. Status: the company confirms the access and extraction, and the volume and content of the data remain a claim.
TSMC said in a Form 6-K filed with the SEC on November 12 that some current and former employee data had been made available on an external website without authorization, and that it matched data stored in the system services of a cloud service provider. It has found no evidence that its own systems were compromised8. Status: confirmed in the filing. The provider, the access method and the number of people affected are not disclosed.
Sega disclosed on November 9 that Arara, the company that sends some of its newsletters, had suffered unauthorized access and that about 2.2 million subscriber email addresses had leaked, a small share of them with delivery-related information. SEGA Account addresses use a different system9. Status: confirmed by Sega as Arara’s customer, cause under investigation at Arara.
Quantum Systems, a German maker of military drones, said on November 12 that it had identified an active cyberattack by “hostile actors” at the end of October and contained it with the authorities10. BleepingComputer, citing Der Spiegel and the Financial Times, reports that the compromise came through a malicious update file for QBase, the company’s ground-control and mission-planning software, delivered to customers, and cites further reports that the German armed forces grounded the drones as a precaution11. Status: the attack is confirmed by the company. The update path and the grounding are press reports.
Revenio Group said on November 9 that an attack had hit the IT systems of its French subsidiary Visionix, on a server holding internal IT service requests, and that it acted to contain the attack to that local server. Its current assessment is that the group’s other operations are unaffected12. Status: confirmed by the company, vector not disclosed.
The ScreenConnect attacks through managed service providers are covered in the security issue for the same week, as is ESET’s research on Turla’s Cereal toolset. On November 11 Romania’s intelligence service said it had identified and stopped, in December 2025, an attempted compromise of a national government institution. SRI names Turla only by citing public reports. The attackers exploited vulnerabilities in Microsoft operating systems, the affected email service was remediated and no exfiltration of sensitive data was identified13. Status: confirmed by the government.
Our recommendation is to give inherited, outsourced and subsidiary systems the same inventory, owner and network boundary as the systems you run directly. Maersk reports no impact on its customer and partner integrations, and that separation is the one to design for. Ask every provider that holds staff or customer data how fast it will notify you and what it keeps, and stage vendor updates for management software, appliances, firmware and agents through a test ring, with an alert when an update arrives outside the vendor’s normal schedule.
Building controllers are infrastructure too
On November 9 France’s cyber crisis coordination center (C4) attributed the attack of October 11 and 12 on industrial refrigeration controllers to Shahid Kaveh, a unit of the Iranian Revolutionary Guard’s electronic and cyber center. On the night of October 11 to 12 the controllers of about 700 retail sites in France were compromised and their defrost settings changed to high temperatures, causing heavy stock losses and, in at least 15 cases, fires. Equipment at small hydroelectric plants was targeted at the same time with moderate effects. CERT-FR notes that the operators used FOFA, a search engine for internet-facing devices, and its report does not specify how they got in14. Status: attributed by the French government, initial access not described.
A data center runs on the same kind of equipment. Our recommendation is to put cooling controllers, chillers, building management, PDUs and UPS network cards on an isolated management network with no direct internet exposure, change their default credentials, route vendor remote access through a controlled jump path, and make sure critical alarms cannot be silenced from the same interface an attacker would use to change setpoints.
Hospitals running degraded
The district of Greiz in Thuringia reported a hacker attack on the Greiz-Ronneburg district hospital, discovered on Sunday, November 15 at about 9 a.m. Police and prosecutors are involved, and the Greiz emergency department was unavailable, with emergencies routed through the regional dispatch center15. Status: confirmed by the district, quoting the hospital management. The vector and whether data was taken are not disclosed.
In Belgium, UZ Brussel says the failure was not an attack. From 11 a.m. on November 10, network problems cut UZ Brussel and three hospitals in Antwerp, Lier and Tielt off from PrimUZ, the electronic patient record system they share. Staff worked with pen and paper, UZ Brussel postponed scheduled operations and ambulances were diverted to other hospitals16. At 11 a.m. on November 11 UZ Brussel reported the network working again, said there was no cyberattack and no data breach was found, and said its partner hospitals were restarting their systems17. The hospital in Tielt confirmed the same day that the problems around the patient record were resolved18. Status: confirmed by the hospitals, technical cause not disclosed.
One cause was malicious and one was not, and both disrupted care and emergency routing. Our recommendation is to test the business fallback along with the VM and backup restore: read-only copies of the records that matter, paper procedures people have used, a second communication channel and a clear rule for when to divert work.
What to check this week
Start with the failover and containment paths, since last week showed both failing under real load. Figure 1 shows how a failover onto a degraded target spread, and Figure 2 sorts every item in this issue by what to do this week.
- For each failover pair, check that the surviving side can carry the failover load plus whatever is already out, counting CPU, memory, network and placement rules, and when the boundary between fault domains was last tested.
- Sign in with the break-glass accounts for vCenter, NSX, SDDC Manager, backup and cloud consoles with the external identity provider and any federation service in front of it unreachable, and fix any that fail.
- Check the enabled zones, healthy targets per zone and cross-zone settings of your load balancers, and that a restart plan brings capacity back behind rate limits.
- Review change control for provider work at remote sites, load-test rate limits and storm control at site edges, and rehearse isolating one site.
- List the services that stop when a central portal or identity service is restricted, and decide which of them can run degraded with local accounts.
- Give acquired systems and third-party services holding staff or customer data an owner, a boundary and a notification commitment, and stage vendor updates through a test ring.
- Confirm that cooling, building management, PDU and UPS controllers have no internet exposure and no default credentials, and that their alarms cannot be muted from the same interface.
- Rehearse the business fallback for the systems that matter most, and work through the ScreenConnect checklist in the security issue for the same week.
Redundancy that was never tested while degraded, and boundaries that were never tested under load, are assumptions until an incident checks them.
Sources
Show all 18 sources
- Preliminary Post Incident Report for Microsoft 365, EX1550543/MO1550821 (Microsoft, November 15, 2026, copy published by Next.ink)
- AWS Health Dashboard: Increased Connectivity issues in US-EAST-1 (November 15, 2026)
- Nationwide Ground Stop: Questions and Answers
- Investigation into Cyber Incident at Lithuanian Customs Identifies Potential Personal Data Breach, BAP Unavailable
- Access to BAP Restored
- IT security incident
- Maersk confirms data breach as WhiteArmor ransomware demands $5 million
- TSMC Form 6-K: statement regarding employee data (November 12, 2026)
- 業務委託企業への不正アクセスによる個人情報流出に関するお詫びとお知らせ
- Statement on Cyber Incident
- German military drone operations disrupted by cyberattack
- Revenio’s subsidiary in France subject to cyberattack
- Atac cibernetic oprit în urma intervenției Centrului Național Cyberint
- CERTFR-2026-CTI-009: Activités cyber offensives ciblant la France menées par des acteurs iraniens liés au CGRI
- Hacker-Angriff auf Kreiskrankenhaus Greiz-Ronneburg
- UZ Brussel among hospitals experiencing severe network problems
- Netwerkproblemen in het UZ Brussel – update 11/11 – 11 uur
- Update: netwerkprobleem opgelost